Solar cooling systems have the advantage of the coincidence between the hours of cooling demand and the hours of solar radiation availability, and they can contribute to reduce the energy consumption in buildings. However, the high cost of thermal solar cooling facilities with absorption chillers, maintenance issues, legionella risk and water consumption (associated to the necessary cooling tower) have limited the use of these systems to demonstration projects. A simplified Transient System Simulation Tool (TRNSYS) model was developed to provide the owner of the demonstration facility the information he needs for design decision-making. This model was validated with experimental data registered in a solar cooling system designed and built by the authors. Different collector field surfaces, hot water storage tank volumes, and absorption machine driving temperatures were analyzed for a hotel demonstration facility. In terms of the energy delivered to the absorption chiller the optimum dimensioning corresponded to the lowest values of the driving temperature (75 °C) and specific storage volume (15 Lm2). From an economic point of view, the saving of 1515 euros per year when compared with an electric compression chiller does not compensate the investment of 3000 euros per kW of cooling capacity that cost the thermal solar cooling facility.
This work focused on a compound PV/T waste heat driven ejector-heat pump system for simultaneous data centre cooling and waste heat recovery for district heating. The system uses PV/T waste heat as the generator’s heat source, acting with the vapour generated in an evaporative condenser as the ejector drive force. Conventional and advanced exergy and advanced exergoeconomic analyses are used to determine the cause and avoidable degree of the components’ exergy destruction rate and cost rates. Regarding the conventional exergy analysis for the whole system, the compressor represents the largest exergy destruction source of 26%. On the other hand, the generator shows the lowest sources (2%). The advanced exergy analysis indicates that 59.4% of the whole system thermodynamical inefficiencies can be avoided by further design optimisation. The compressor has the highest contribution to the destruction in the avoidable exergy destruction rate (21%), followed by the ejector (18%) and condenser (8%). Moreover, the advanced exergoeconomic results prove that 51% of the system costs are unavoidable. In system components cost comparison, the highest cost comes from the condenser, 30%. In the same context, the ejector has the lowest exergoeconomic factor, and it should be getting more attention to reduce the irreversibility by design improving. On the contrary, the evaporator has the highest exergoeconomic factor (94%).