Fire resistant door assemblies (doors) for pedestrian or industrial traffic with frame, leaf or leaves, rolled or folded curtain etc. are designed for installation in the openings of the building’s vertical internal partitions. The building and its associated equipment shall be designed and made so that in case of fire it ensures the necessary load bearing capacity of the structure for the time specified in national regulations, limitation of fire and smoke propagation within the building, limitation of fire propagation onto the adjacent buildings and evacuation of people, and it provides safety of the rescue teams. The mentioned requirements are not usually considered individually (e.g. ensuring proper evacuation is connected with the structural load bearing capacity, fire and smoke propagation within the building, and rescue team safety), therefore individual elements of buildings can play several roles during a fire.This also refers to the building elements such as doors which are usually required in terms of design and execution to ensure that in case of fire they shall, for a specific period of time prevent its development from the room or a specific zone where the fire started to other rooms or zones, allow evacuation of people by limiting heat radiation, and facilitate rescue team activities. Therefore, fire doors have a major role in the fulfillment of the rules of buildings fire safety.This paper discusses the main issues related to the fire resistance of fire doors (tests methodology and way of classification) and presents a comparison of temperature rises on unexposed surface of fire doors test specimens depending on the type of structure and side of fire exposure. Temperature rises have been compared on unexposed surface of timber, aluminum and steel single leaf doorset which have fulfill the requirements of the EI2 30 fire resistance class, in case of the fire acting from the hinge side and the side opposite to the hinges.
This paper discusses the main issues related to the fire resistance of aluminium glazed curtain walls including the tests methodology and way of classification of this type of building elements. Moreover, the paper presents the comparison of fire resistance test results of large test specimens of curtain walls in full configuration depending on the side of fire exposure. Temperature rises have been compared on unexposed surface of the curtain walls tested for standard and external fire exposure. To made the comparison four test specimens of glazed aluminium curtain walls in full configuration, were tested. Curtain walls had the same transom – mullion structure. Two test specimens were tested for external fire exposure, and two for standard fire exposure. Dimensions of exposed surfaces were 5000 x 4500 mm (width x height) for external fire exposure and 5000 x 4800 mm (width x height) for internal fire exposure.
Arguably, one of the most important requirement a building have to meet in case of fire is to ensure the safe evacuation of its users and the work of rescue teams. Consequently, issues related to the risks associated with falling parts of facades are fairly well known around Europe. Even though not equally well defined as other fire safety requirements concerning glazed facades, there is plenty of test methods for assessment of facades regarding falling parts, mostly based on an approach related to fire spread. In this paper selection of test method for assessment of facades regarding falling parts is briefly presented. However, focus of this work is on fire test of typical glazed segment of façade performed in ITB Laboratory. Results of the test positively verifies conjecture that solutions with glass units configured with thin, tempered glass panes on the outer side should pose no threat. However, the question has been raised whether the behaviour of other glass unit solutions (with additional coatings or laminated) would be similar.