1 June 2019 in Research Papers Faculty of Materials Science and Technology Slovak University of Technology
This scientific study deals with investigation of the heat of combustion and effective heat of combustion of selected electrical cables. Two different electrical cables for rated voltage of 0.6/1 kV were investigated. Both cables were power three-core with cross-section area of each core of 1.5 mm 2 . The cores of both cables were made of a bar cooper wire. Insulations of conductors of both cables were made of silane cross-linked polyethylene without any inorganic filler, while the bedding and outer sheath were made of polyethylene-based copolymer (the beddings were filled with two fillers - aluminium hydroxide and calcium carbonate, while the outer sheath were filled only with aluminium hydroxide). Reaction to fire class of both cables was B2 ca , s1, d0, a1. The main difference in the investigated cables was that the core of one of them was wrapped in a glass mica tape (this cable showed circuit integrity maintenance under fire conditions during 180 minutes). The heat of combustion and effective heat of combustion were determined by the oxygen bomb calorimeter according to the ISO 1716:2018 standard. The highest effective heat of combustion showed the insulation of wires (for both cables 42.47 ± 0.03 MJ/kg), lower value showed outer sheath (interval form13.61 to 15.26 MJ/kg) and the lowest value was determined for bedding (interval from 4.69 to 6.39 MJ/kg). The effective heath of combustion per unit of length of both investigated cables lies in the interval from 1.37 to 1.38 MJ/m. Therefore, there is no significant difference in effective heats of combustion of the electrical cables investigated.
1 June 2021 in Research Papers Faculty of Materials Science and Technology Slovak University of Technology
This study deals with the Fire Growth Rate Index (FIGRA) as a key fire characteristic of electrical cables (determined by a cone calorimeter) that allows to estimate their reaction to fire class. Three power (supply) electrical cables (reaction to fire class B2ca) were tested by a cone calorimeter using different heat fluxes of 20, 30, 40 a 50 kW·m−2. The cables were three-wire (cross-section of each wire was 1.5 mm2) with a nominal voltage of 0.6 kV (alternating current), resp. 1 kV (direct current). The cable sheaths were made of an ethylene copolymer filled with aluminum hydroxide. The beddings were made of an ethylene copolymer filled with a mixture of aluminum hydroxide and calcium carbonate. The conductor insulations of one electrical cable were made of crosslinked polyethylene and the conductor insulations of the other two electrical cables were made of an ethylene copolymer filled with aluminum hydroxide. FIGRA was determined per unit length and unit area of electrical cables. FIGRA increased with increasing heat flux. At a heat flux of 50 kW·m−2, all the electric cables examined showed a very similar FIGRA (from 0.19 to 0.21 kW·m−1·s−1 and 18.4 to 21.2 kW·m−1·s−1, respectively). Conversely, at a heat flux of 20 kW·m−2, the investigated cables showed greater FIGRA variance (in the range of 0.11 to 0.16 kW·m−1·s−1 or 10.8 to 16.2 kW·m−1·s−1).