This paper develops a generalized ac impedance model for synchronous generators and then a dc impedance model for generator-thyristor systems. The impedance model of a medium voltage dc (MVdc) system is built for impedance-based stability and harmonics analysis. DC current harmonics from a high-power neutral point clamped (NPC) direct torque control (DTC) motor drive is examined. It is found that dc network resonance is a major cause of dc current harmonics amplification and propagation in MVdc systems. As a result, adding a dc side input filter can attenuate current harmonics from NPC DTC drives. Three criteria to design the dc-side filter are deduced from the impedance analysis. The effectiveness of the design criteria is tested and verified by time-domain simulations.
3 August 2023 in IEEE Transactions on Industry Applications
This paper presents a small-signal stability analysis tool for large-scale power systems with high penetration of inverter-based resources (IBRs). Firstly, a network transfer function matrix (NTFM), which represents the information of the system topology, transmission lines, loads, IBRs locations, etc., is derived to model the entire power system network. Secondly, small-signal perturbation method is applied to obtain the sequence impedance/admittance models of the block-box IBRs considering the frequency cross-coupling effects. With the obtained NTFM as well as IBR models, a multi-input, multi-output (MIMO) feedback system is constructed, and the generalized Nyquist criterion (GNC)-based stability method is employed to analyze the stability of the entire power system. Furthermore, based on the developed stability analysis method, sensitivity analysis is conducted on an unstable case to identify which parameter has a high impact on the system stability. Different test cases based on a modified IEEE 14-bus system as well as a reduced 240-bus WECC system are studied to verify the proposed stability analysis tool.
Co-simulation offers a time-efficient method for ac-curately analyzing the behavior of distribution systems dominated by inverter-based resources (IBRs). However, most co-simulation studies in the literature overlook distribution grids. Additionally, these studies do not discuss practical IBR models nor how to ini-tialize the interface model variables of co-simulation platforms. To obtain co-simulation results that are reasonably accurate for dis-tribution system-based planning and operation, it is pertinent to develop co-simulation platforms well-suited for studying the accu-rate behavior of IBRs coupled to unbalanced distribution grids. This paper introduces an initialization algorithm for initializing the interface model variables of co-simulation platforms. The ini-tialization algorithm is anchored on leveraging the fast execution speed of the per-phase phasor simulation to quickly pre-calculate initial values of interface model variables prior to starting co-sim-ulation. This paper further proposes the inclusion of rate limiters in the co-simulation platforms interface models to prevent the in-capability of the per-phase phasor simulator to clear faults at zero-crossing of currents from falsely impacting the control system of practical IBR models. The proposed methods are validated by benchmarking the results from a per-phase phasor/electromag-netic transient (EMT) co-simulation of an IBRs-dominated IEEE 34-Node test feeder against the results from a full EMT simulation.