Current approaches for improving LCC-HVDC recovery ability after AC faults operate in isolation, neglecting the combined impacts of reactive power and phase shift on commutation margin. This paper proposes an integrated control combining reactive power control with firing angle correction to enhance LCC-HVDC system self-restoration. Firstly, this paper illustrates the influence of phase offset on commutation margin and analyzes the feasible region of DC transmission power and inverter-absorbed reactive power under the extinction angle control. Then, a method is proposed for modifying LCC-HVDC control considering dynamic reactive power balance and phase offset during AC fault and system recovery period. Specifically, upon AC fault detection, the system dynamically adjusts DC current and extinction angle references through reactive power control, while implementing different phase-offset compensation in different periods for firing angle correction. Additionally, the critical firing angle, satisfying commutation margin requirements at the intersection of reactive power control and extinction angle control, is established as the operational upper limit. Finally, the modified method is tested in the CIGRE HVDC, Guiguang II, Three Gorges-Shanghai and multi-feed DC Project models. Simulation results confirm significant improvements in commutation stability and DC current continuity during AC fault and system recovery.
6 July 2023 in IEEE Transactions on Power Delivery
An existing synchronous firing control is mainly composed of phase-locked loop (PLL), equidistant pulse control (EPC) and area minimum control (AMC), which can accurately predict the firing time in the steady state, while the accuracy deteriorates under AC faults. In this paper, in order to alleviate commutation failures in LCC-HVDC transmission project caused by single-phase-grounding (SPG) fault, the phase offset and the commutation margin under SPG faults are analyzed, and an improved synchronous firing control on suppressing LCC-HVDC commutation failures caused by SPG faults is proposed. First, the forward zero-crossing point of the grid-side non-fault line voltage is used to generate synchronous phases during the fault. Second, the phase offset of commutation voltage that is most likely to make the valve fail to be shut down was determined under SPG faults. Third, the phase offset was used to correct the EPC and the AMC respectively. Finally, in the Three Gorges Shanghai DC project model, the fault tests were carried out in the strong and the weak AC systems respectively. The results show that the improved control can improve the ability of LCC-HVDC projects to suppress commutator failure.
30 August 2022 in IEEE Transactions on Power Delivery
Synchronous reference frame phase-locked loop (SRF-PLL) is adopted in HVDC synchronous firing control to output the synchronous phase. The synchronous performance directly affects the accuracy of the firing pulse, and even affects whether the inverter can successfully commutate during AC asymmetric faults. Therefore, an improved HVDC synchronous firing control method based on order switching and phase compensation is proposed in this paper. The improved SRF-PLL has the functions of extracting the fundamental frequency positive sequence (FFPS) phase and switching the order. When the fault detection detects that a fault has occurred, PLL is converted from the second-order system to the first-order system, so as to shorten the out-of-lock time and make it quickly enter the resynchronization. Then, for the phase shift of commutation voltages caused by fault, the zero-crossing sampling method is used to detect the change of the commutation voltage phases, and the synchronous phase of each commutation voltage is compensated selectively. Finally, the improved method is tested in CIGRE HVDC benchmark model and Three Gorges-Shanghai (3GS) DC project model, respectively. The results show that the improved method has better effect on suppressing commutation failure.
18 December 2023 in IEEE Transactions on Power Delivery
The small-signal admittance model is an important basis for stability analysis of power electronics-dominated system. In contrast to the extensively explored voltage-sourced converter (VSC) modeling in recent years, the accuracy of the admittance model for the line-commutated converter (LCC) is compromised due to inadequate representation of its switching dynamics. In this article, the state function based on single-side modulation is introduced to characterize the conduction state and switching characteristics of the LCC. Combining the linear dynamics of AC and DC variables in each conduction state, the AC/DC admittance matrix considering multi-frequency coupling is further obtained by applying multi-harmonic linearization method. Based on the defined matrix gain, the truncation order of the matrix is determined, and a detailed discussion is conducted on the influence of different modeling methods and factors on the precision of the model. Then, the equivalent admittance considering the coupling between LCC and grid impedance is derived and the influences of operation conditions on which is analyzed. Finally, the equivalent admittance is applied to the stability analysis of a practical project in China Southern Power Grid (CSG), and the predicted resonance shows high accuracy compared with the simulation results.