22 May 2025 in IEEE Transactions on Power Delivery
Current approaches for improving LCC-HVDC recovery ability after AC faults operate in isolation, neglecting the combined impacts of reactive power and phase shift on commutation margin. This paper proposes an integrated control combining reactive power control with firing angle correction to enhance LCC-HVDC system self-restoration. Firstly, this paper illustrates the influence of phase offset on commutation margin and analyzes the feasible region of DC transmission power and inverter-absorbed reactive power under the extinction angle control. Then, a method is proposed for modifying LCC-HVDC control considering dynamic reactive power balance and phase offset during AC fault and system recovery period. Specifically, upon AC fault detection, the system dynamically adjusts DC current and extinction angle references through reactive power control, while implementing different phase-offset compensation in different periods for firing angle correction. Additionally, the critical firing angle, satisfying commutation margin requirements at the intersection of reactive power control and extinction angle control, is established as the operational upper limit. Finally, the modified method is tested in the CIGRE HVDC, Guiguang II, Three Gorges-Shanghai and multi-feed DC Project models. Simulation results confirm significant improvements in commutation stability and DC current continuity during AC fault and system recovery.
1 January 2022 in Journal of Modern Power Systems and Clean Energy
This paper provides a comprehensive analysis of local and concurrent commutation failure (CF) of multi-infeed high-voltage direct current (HVDC) system considering multi-infeed interaction factor (MIIF). The literature indicates that the local CF is not influenced by MIIF, whereas this paper concludes that both the local CF and concurrent CF are influenced by MIIF. The ability of remote converter to work under reduced reactive power enables its feature to support local converter via inter-connection link. The MIIF measures the strength of electrical connectivity between converters. Higher MIIF gives a clearer path to remote converter to support local converter, but at the same time, it provides an easy path to local converter to disturb remote converter under local fault. The presence of nearby converter increases the local commutation failure immunity index (CFII) while reducing concurrent CFII. Higher MIIF causes reactive power support to flow from remote converter to local converter, which reduces the chances of CF. A mathematical approximation to calculate the increase in local CFII for multi-infeed HVDC configurations is also proposed. A power flow approach is used to model the relation between MIIF and reactive power support from remote end. The local and concurrent CFIIs are found to be inverse to each other over MIIF; therefore, it is recommended that there is an optimal value of MIIF for all converters in close electric proximity to maintain CFII at a certain level. The numerical results of established model are compared with PSCAD/EMTDCsimulations. The simulation results show the details of the influence of MIIF on local CF and concurrent CF of multi-infeed HVDC, which validates the analysis presented.
18 December 2023 in IEEE Transactions on Power Delivery
The small-signal admittance model is an important basis for stability analysis of power electronics-dominated system. In contrast to the extensively explored voltage-sourced converter (VSC) modeling in recent years, the accuracy of the admittance model for the line-commutated converter (LCC) is compromised due to inadequate representation of its switching dynamics. In this article, the state function based on single-side modulation is introduced to characterize the conduction state and switching characteristics of the LCC. Combining the linear dynamics of AC and DC variables in each conduction state, the AC/DC admittance matrix considering multi-frequency coupling is further obtained by applying multi-harmonic linearization method. Based on the defined matrix gain, the truncation order of the matrix is determined, and a detailed discussion is conducted on the influence of different modeling methods and factors on the precision of the model. Then, the equivalent admittance considering the coupling between LCC and grid impedance is derived and the influences of operation conditions on which is analyzed. Finally, the equivalent admittance is applied to the stability analysis of a practical project in China Southern Power Grid (CSG), and the predicted resonance shows high accuracy compared with the simulation results.