Oil leakage will cause abnormal temperature rise and discharge of oil-filled power equipment, which seriously threatens insulation reliability. In this paper, based on the synchronous fluorescence spectra (SFS) and excitation emission matrix (EEM) of mineral and vegetable oils, the ultraviolet-induced hyperspectral imaging (UV-induced HSI) measurement system is developed. Then, the fluorescence-reflectance spectra of oil traces and non-oil areas are determined via the proposed measurement system. Next, the influence factors of fluorescence-reflectance intensity, including UV source light power, detection angle degree and detection distance are discussed. By analyzing the fluorescence-reflectance intensity differences in fluorescence bands, principal component analysis (PCA) is applied for date dimension reduction and anomaly detection to realize oil leakage trace visualization. Finally, the validation test results prove that this method exhibits a general applicability for tracing mineral and vegetable oil leakage traces on different surface materials in indoor and outdoor conditions. This approach will improve the detection rate of oil leakage defects, and promote the intelligent level of operation and maintenance of power equipment.
2 June 2023 in Journal of Physics D: Applied Physics
The application of high temperature vulcanized (HTV) silicone rubber materials in transmission lines insulators has been extensive. However, with the accumulation of pollution and moisture on the surface of HTV silicone rubber, the insulation reliability gradually decreases, which may even lead to flashover. In this paper, hyperspectral imaging technology is utilized as a rapid and effective tool for the visual characterization of pollution and moisture parameters of the polluted HTV silicone rubber. Based on the analysis of reflection spectra, it has been determined that the pollution degree has a positive effect and the moisture content has a negative effect on the reflection characteristics of HTV silicone rubber, respectively. Further quantitative analysis of reflectance values at various moisture conditions reveals that exponential relationships can be observed between reflectance values and moisture contents at a certain wavelength. At the same time, linear correlations between reflectance values and pollution degrees (quantified as equivalent salt deposit density (ESDD)) at a certain wavelength are also proposed. By integrating the exponential and linear relationships, a double-exponential model is formulated to concurrently characterize the ESDD and moisture content (MC). Furtherly, from the perspective of engineering application, to enhance the model’s robustness, a set of equations combining spectral indexes and spectral shape feature parameters is initially formulated for the calculating of ESDD and MC. Given the synchronous inversion and visualization capabilities of pollution and moisture parameters of the polluted HTV silicone rubber surface, the visual characterization model serves as a valuable tool for protecting against pollution flashover failures and designing power equipment insulation.