27 December 2018 in Energy Efficiency
13 March 2024 in IEEE Transactions on Industry Applications
Successful discrimination of, isolation from, and recovery against short-circuit electrical faults within microgrids having distributed energy resources (DERs) is challenging, as protection coordination must include not only the distribution equipment, but also control and low voltage ride-through settings of DERs. This is especially the case when grid resilience is improved by use of the microgrid to maintain services from DERs (localized to an installation) following utility grid outages. Under islanded configurations, continued reliability of power delivery is essential, even in the face of subsequent electrical faults. The main purpose of this paper is to propose a novel protection design process, and to demonstrate it on an islanded ac microgrid with parallel feeders. The contribution is a methodology for coordinated circuit breaker protection and ride-through settings, thereby maximizing the post-fault recoverability of an ac microgrid subject to faults in an islanded configuration. The aim is improve the microgrid resilience in islanded configurations. The protection and IEEE Standard 1547-2018 ride-through settings are validated in controller hardware-in-the-loop simulation, validating the proposed design process. Additionally, detailed implementation of ride-through enabling controls are discussed.
26 April 2021 in IEEE Open Journal of Power Electronics
Silicon carbide (SiC) devices can exhibit simultaneously high electro-thermal conductivity and extremely fast switching. To perform optimal designs showing the benefits of SiC in achieving efficiency, size, weight, and cost objectives for electric converters design, it is necessary to establish better models for calculating device losses and an efficient thermal model that can be calibrated to consider the nuances of measurement based thermal equivalent circuits. This work's outputs can be used in a power converter multi-objective optimization process or real-time temperature prediction of drives to improve reliability and maximize performance. The proposed modified loss calculation and thermal model demonstrate the SiC power module's advantages to reduce peak junction temperature and power cycling effects. A detailed power loss calculation and thermal model is developed and tested on a 480 V, 186 A, 150 HP variable frequency drive (VFD) with SiC modules. A comparison between the SiC module and an equivalent rated Si module demonstrates the reduction in power cycling effects, particularly at low-speed operation. Infrared (IR) imaging results and analytical explanations of the phenomenon is provided. Power cycle tests show that higher thermal conductivity is not the only reason contributing to the lower temperature ripple in low-speed operation.
9 July 2018 in IEEE Transactions on Industrial Electronics
Fault current limiters (FCLs) are one of the main solutions to upcoming challenges in the microgrid protection. Regarding the high penetration of distributed generations (DGs) in the future power system, designing cheap and effective FCLs is a necessity. This letter addresses this issue by proposing an embedded FCL operating based on modifying the secondary control of the inverter. As this method is presented for a four-wire system, besides very low implementing cost, it has independency and flexibility to only limit the current of the DG faulted phase. This letter also provides real-time simulation results by real time simulator (OPAL-RT) to compare the proposed method with a virtual-impedance-based FCL to validate its effectiveness. Finally, experimental results are presented to validate the effectiveness of the proposed FCL.
2 June 2021 in IEEE Transactions on Industry Applications
This article compares the performance of different detection methods for a single-phase inverter interfacing a distributed energy resource during abnormal transients or failures of the utility electric power system voltage. The performance of the various methods is presented and compared to IEEE Standard 1547-2018 requirements using a physics-based model. Simulation scenarios are created to compare controller responses to intentional islanding and ride-through recommended timing specified in IEEE Standard 1547-2018. Additionally, four voltage abnormality detection methods were implemented in a Field Programmable Gate Array (FPGA)-based controller hardware-in-the-loop simulation and assessed for steady state and transient performance, and FPGA resource utilization. Finally, the physics-based model is validated by experimental measurements on a laboratory prototype with an FPGA-based controller.
15 May 2020 in IEEE Transactions on Industry Applications
This paper identifies validates the use of ultra-fast SiC JFET based self-powered solid state circuit breakers (SSCBs) as the enabling protective device for a 340Vdc residential DC community microgrid. These SSCBs will be incorporated into a radial distribution system in order to enhance fault discrimination through autonomous operation. Because of the nature and characteristics of short circuit fault inception in DC microgrids, the time-current trip characteristics of protective devices must be several orders of magnitude of faster than conventional circuit breakers. The proposed SSCBs detect short circuit faults by sensing the sudden voltage rise between its two power terminals and draw power from the fault condition itself to turn off SiC JFETs and then coordinate with no load contacts can isolate the fault. Depending upon the location of the SSCBs in the microgrid either unidirectional or bidirectional implementations are incorporated. Cascaded SSCBs are tuned using a simple resistor change to enable fault discrimination between upstream high current feeds and downstream lower current branches. Operation of one of the SSCBs and three in cascaded arrangements are validated both in simulation and with a hardware test platform. Thermal impact on the SSCB is discussed as well. The target application is a residential DC microgrid that will be installed as part of a revitalization effort of an inner city Milwaukee neighborhood.