Intelligent condition monitoring of Direct Current (DC) to DC converters requires fault detection that is accurate, reproducible and early enough to act before conventional protection trips. This paper presents a Random Forest (RF) framework that fuses output-voltage, inductor-current and heatsink-temperature measurements of a 48 V/10 A synchronous buck converter (96 V input, 20 kHz switching, cascaded PI control). A fully specified averaged-model simulation with sensor models (10 kHz sampling) and per-run component tolerances generates 200 labelled runs (40 per class, 60 s each; 59,000 windows of 0.2 s) covering normal operation, overcurrent (13.8–15.2 A), overvoltage (55.5–59.0 V), overtemperature caused by cooling degradation, and a combined severe fault. Ten features are extracted per window, including ripple factors, ripple Total Harmonic Distortion (THD), temperature slope and a thermal-model residual. A five-class RF (128 trees, maximum depth 14) tuned by Bayesian optimisation under run-wise cross-validation achieves 97.9% accuracy and 98.1% macro-F1 on 60 independent test runs (16,843 windows), and 97.7 ± 1.4% accuracy in repeated group 5-fold cross-validation. A tuned support vector machine attains higher in-distribution accuracy (99.5%), whereas RF gives the highest mean accuracy (98.0%) under six unseen operating conditions. Fusing electrical and thermal features raises accuracy from 70.2% (electrical only) and 75.4% (thermal only) to 97.9%. With a three-window alarm rule, all 48 test faults are flagged before the conventional trip threshold is crossed, with mean lead times of 3.9 s (overcurrent), 7.5 s (overvoltage), 26.5 s (overtemperature) and 2.5 s (severe fault). A classifier-weighted Fault Severity Index (FSI) rises from 0.04 in normal operation to 2.62 under severe fault, providing a quantitative severity ranking.