This paper presents a method for rapid detection of faults on voltage source converter multiterminal HVdc transmission networks using multipoint optical current sensing. The proposed method uses differential protection as a guiding principle, and is implemented using current measurements obtained from the optical current sensors distributed along the transmission line. Performance is assessed through detailed transient simulation using MATLAB/Simulink models, integrating inductive dc-line terminations, detailed dc circuit-breaker models, and a network of fiber-optic current sensors. Moreover, the feasibility and required performance of optical-based measurements is validated through laboratory testing. Simulation results demonstrate that the proposed protection algorithm can effectively, and within very short period of time, discriminate between faults on the protected line (internal faults), and those occurring on adjacent lines or busbars (external faults). Hardware tests prove that the scheme can be achieved with the existing, available sensing technology.
In this paper, a sensor that is capable of measuring both ac current and temperature using a single fiber Bragg grating (FBG) is described. The device consists of a magnetically biased magnetostrictive alloy bonded to an FBG. The magnetic field generated by the current in a specially designed coil produces internal strains in the magnetostrictive alloy which can be detected by the FBG. The temperature at the sensing point is determined through averaging of the sensor output signal. The measurement range of the sensor can be varied by altering the design of the sensor coil. A prototype sensor that is capable of measuring ac currents up to 1 A has been constructed while simultaneously measuring temperatures of up to 100 degC
17 October 2017 in IEEE Transactions on Smart Grid
This paper presents a new method for locating faults in multi-terminal direct current (MTDC) networks incorporating hybrid transmission media (HTMs), including segments of underground cables (UGCs) and overhead lines (OHLs). The proposed travelling wave (TW) type method uses continuous wavelet transform (CWT) applied to a series of line current measurements obtained from a network of distributed optical sensors. The technical feasibility of optically-based DC current measurement is evaluated through laboratory experiments using Fiber-Bragg Grating (FBG) sensors and other commercially available equipment. Simulation-based analysis has been used to assess the proposed technique under a variety of fault types and locations within an MTDC network. The proposed fault location scheme has been found to successfully identify the faulted segment of the transmission media as well as accurately estimating the fault position within the faulted segment. Systematic evaluation of the method is presented considering a wide range of fault resistances, mother wavelets, scaling factors and noisy inputs. Additionally, the principle of the proposed fault location scheme has been practically validated by applying a series of laboratory test sets.
After the occurrence of a DC-side feeder faults on HVDC transmission systems, protection and fault detection systems are anticipated to minimize their onerous effects, by initiating fault-clearing actions such as selective tripping of circuit breakers. Following the successful fault clearance, a subsequent action of significant importance, is the meticulous estimation of its location as a means to accelerate the line restoration, reduce down-time, limit recovery and repair costs, and hence elevate the overall availability and reliability of the transmission system. In order to capture DC-side fault transients for protection and fault location applications, measuring equipment is required to be placed on HVDC installations. This paper focuses primarily on reviewing the available technologies from the perspective of enabling protection, fault location and automation applications in HVDC systems. The review constitutes a mapping of protection and fault location functions, against the available voltage and current measuring technologies, ultimately unlocking insights for selecting measuring equipment based on the desirable characteristics of protection and fault location systems. The review also revealed that the frequency characteristics of each sensing scheme, primarily refers to the bandwidth of the primary sensor, whereas the overall bandwidth of the complete measuring scheme may be further restricted by the secondary converter and corresponding data acquisition system and signal processing electronics. It was also identified that the use of RC voltage dividers has prevailed for voltage measurements for HVDC applications, due to their superior advantages. The choice of a suitable device for current measurement, depends mainly on the fault detection method used and the frequency range it operates. In particular, the review revealed that fault detection and protection methods are mainly concentrated in a frequency spectrum ranging from a few kHz to 100 kHz, while fault location methods require measurements with a frequency range from 100 kHz up to 2 MHz.
1 April 2018 in International Journal of Electrical Power & Energy Systems