Distribution networks are evolving toward the vision of smart grids, with increasing penetration of distributed generation (DG), introduction of active network management (ANM), and potentially islanded modes of operation. These changes affect fault levels and fault current paths and have been demonstrated to compromise the correct operation of the overcurrent protection system. This paper presents an adaptive overcurrent protection system which automatically amends the protection settings of all overcurrent relays in response to the impact of DG, ANM, and islanding operation. The scheme has been developed using commercially available protection devices, employs IEC61850-based communications, and has been demonstrated and tested using a hardware-in-the-loop laboratory facility. A systematic comparison of the performance of the proposed adaptive scheme alongside that of a conventional overcurrent scheme is presented. This comparison quantifies the decrease in false operations and the reduction of mean operating time that the adaptive system offers.
Inverter-dominated microgrids impose significant challenges on the distribution network, as inverters are well known for their limited contribution to fault current, undermining the performance of traditional overcurrent protection schemes. This paper introduces a new protection scheme based on the initial current traveling wave utilizing an improved mathematical morphology (MM) technology, with simplified polarity detection and new logics introduced for meshed networks and feeders with single-end measurement. The proposed protection scheme provides ultrafast response and can be adapted to varied system operational modes, topologies, fault conditions, and load conditions. Only low-bandwidth communication is required to achieve high-speed operation and adequate discrimination level in meshed networks. Simulation in PSCAD/EMTDC verifies both the sensitivity and stability of the proposed protection scheme under different microgrid operational scenarios.
28 March 2018 in IEEE Transactions on Power Electronics
High-Voltage Direct Current (HVDC) systems are being widely employed in various applications because of their numerous advantages such as bulk power transmission, efficient long-distance transmission, and flexible power-flow control. However, Line-Commutated Converter (LCC) based HVDC systems suffer from commutation failure which is a major drawback, leading to increased device stress and interruptions in transmitted power. This paper proposes a predictive control strategy, deploying a Commutation Failure Prevention Module (CFPM) to mitigate the commutation failures during AC system faults. The salient feature of the proposed strategy is that it has the ability to temporarily decrease the firing angle of thyristor valves depending on the fault intensity to ensure a sufficient commutation margin. In order to validate the performance of the proposed strategy several simulations have been conducted on CIGRE Benchmark HVDC model using PSCAD/EMTDC software. Additionally, practical performance and feasibility of the proposed strategy is evaluated through laboratory testing, using the real time Opal-RT hardware prototyping platform. Simulation and experimental results demonstrate that the proposed strategy can effectively inhibit the commutation failure or repetitive commutation failures under different fault types, fault impedances and fault initiation times.
26 December 2016 in IEEE Transactions on Power Delivery
This paper presents a method for rapid detection of faults on voltage source converter multiterminal HVdc transmission networks using multipoint optical current sensing. The proposed method uses differential protection as a guiding principle, and is implemented using current measurements obtained from the optical current sensors distributed along the transmission line. Performance is assessed through detailed transient simulation using MATLAB/Simulink models, integrating inductive dc-line terminations, detailed dc circuit-breaker models, and a network of fiber-optic current sensors. Moreover, the feasibility and required performance of optical-based measurements is validated through laboratory testing. Simulation results demonstrate that the proposed protection algorithm can effectively, and within very short period of time, discriminate between faults on the protected line (internal faults), and those occurring on adjacent lines or busbars (external faults). Hardware tests prove that the scheme can be achieved with the existing, available sensing technology.
15 December 2009 in IEEE Transactions on Power Systems
A step-by-step coordinated design procedure for power system stabilisers (PSSs) and automatic voltage regulators (AVRs) in a strongly coupled system is described in this paper. It is shown that it is possible to separate the design of individual PSSs and separate the design of individual AVRs. Thereby, the designs of AVR and PSS devices at a given machine can be coordinated to achieve near-optimal overall power system stability performance, including oscillation stability performance and transient stability performance. The proposed coordinated PSS/AVR design procedure is established within a frequency-domain framework and serves as a most useful small-signal complement to established large-signal transient simulation studies.
When faults occur in the microgrids, high frequency transients will be superimposed on the system currents and voltages. The magnitude of those transients will attenuate as it encounters the discontinuity points in the network such as busbars, or any other impedance discontinuity points. This phenomenon can also be quantified by wavelet energy, which provides a useful tool to detect faults and locate the faulted feeder in the microgrid. In this paper, a novel protection scheme based on the transient wavelet energy of the superimposed current extracted by the Maximal Overlap Discrete Wavelet Transform (MODWT) algorithm is developed to detect faults and locate the faulted feeder in microgrids. Compared with existing protection schemes, the proposed protection scheme has the advantage of being largely immune to the changes in system fault level, fault types and positions, microgrid operating status and the control strategies deployed on the inverters, while presenting much lower requirement on the sampling frequency (10 kHz) compared with travelling wave-based methods. Unlike the conventional differential protection, the proposed scheme does not require synchronized measurement or high bandwidth communication channels, and thus, it can be considered as an economical and promising solution for microgrids.