16 August 2024 in Energies
Verified
Journal Article
Open access
PDF file
DIDauren Dzhambulovich Issabekov
Dauren Dzhambulovich Issabekov
AKAleksandr Kislov
Aleksandr Kislov
VMVadim Pavlovich Markovskiy
Vadim Pavlovich Markovskiy
NZNurlybek Shakaevich Zhumataev
Nurlybek Shakaevich Zhumataev
AZAliya Zhumadirova
Aliya Zhumadirova
DNDamir Narynbayev
Damir Narynbayev
Construction of relay protections of electrical installations without the use of bulky metal- and insulation-intensive measuring current transformers (CTs) was repeatedly discussed at Conferences of the International Council on Large Electric Systems (CIGRE) as a challenge for the electric power industry. In the article, the authors present resource-saving reed switch current protection for 6–10-kV electrical installations connected to switchgear cells, which is an alternative to traditional protections. The scientific novelty of the work lies in (a) reed switch protection design on the basis of measuring the magnetic induction in different modes and at different points inside a cell, and we prove that inductance values are sufficient to detect phase short-circuits in electrical installations fed from this cell and derive the dependence of the induction on the position of an inductance coil inside the cell; (b) proven possibility of using the simplest formula of the Biot–Savart law for the calculations if the experimentally obtained coefficients are introduced into it; (c) development of a technique for calculating the parameters of the overcurrent protection based on reed switches. Experimental results are presented in graphical form and clearly show the points of EMS maxima and minima. Settings for resource-saving current protection are selected and a feasibility study of the effectiveness of resource-saving overcurrent protection is carried out. A technical and economical assessment of the efficiency of the suggested overcurrent protection is conducted.

3 April 2024 in Energies
Verified
Journal Article
Open access
PDF file
EKEvgeniy Kolesnikov
Evgeniy Kolesnikov
ANAleksandr Novozhilov
Aleksandr Novozhilov
DRDilara Rakhimberdinova
Dilara Rakhimberdinova
AKAleksandr Kislov
Aleksandr Kislov
TNTimofei Novozhilov
Timofei Novozhilov
In this work, a mathematical model of a three-phase nonlinear transformer is suggested. The model enables simulating the transformer operation with allowance for its nonlinearity and covers needs of the relay protection. Our model has been developed on the basis of a mathematical model with phase coordinates, where differential equations are composed by the Kirchhoff’s phase-voltage law. Based on this model, we first compose a mathematical model for simulating steady-state operation modes of a transformer, taking into account the asymmetry and nonlinearity of its ferromagnetic core. In this model, the initial values of inductances and mutual inductances of loops are determined from the main phase inductance calculated by the experimentally found no-load current, and their current values are determined from the currents in windings and the magnetic fluxes in legs of the transformer core. The magnetic fluxes are calculated by the nodal-pair method. This improved mathematical model is verified through a comparison between the calculated harmonic components of the phase currents and the experimental results. The harmonic components are calculated with the use of Fourier expansion of the calculated phase currents. Their experimental values are determined with a spectrum analyzer. The calculated and experimental harmonic components of the currents of phase A during no-load and rated-load operation of the transformer are tabulated. The comparison of these results shows that the mathematical model of a three-phase transformer we suggest makes it possible to simulate currents in transformer windings under steady-state operation modes with accuracy acceptable for relay protection.

29 November 2023 in Energies
Verified
Journal Article
Open access
PDF file
DRDilara Rakhimberdinova
Dilara Rakhimberdinova
ANAleksandr Novozhilov
Aleksandr Novozhilov
EKEvgeniy Kolesnikov
Evgeniy Kolesnikov
OAOksana Andreeva
Oksana Andreeva
OTOlzhas Manarbekovich Talipov
Olzhas Manarbekovich Talipov
AKAleksandr Kislov
Aleksandr Kislov
The design features of high-power ore furnaces are the transformer’s secondary winding made of 4–8 isolated splits and a busbar assembly made of the same number of paired bifilar bus tubes, spaced 20–40 mm apart. Only an arc fault (AF) can occur between paired bus tubes in such an assembly, during which the assembly with currents of 35–150 kA can be completely destructed. To protect against AFs, these bus tubes are wrapped in several layers of gluey fiberglass cloth. However, such cloth is abraded under the impact of airborne abrasive dust particles during furnace operation, and coal dust in the air creates the conditions for an AF. A new current protection with a magnetic current transformer (MCT), which prevents busbar assembly destruction, is suggested. Its design is based on the analysis of the distribution of busbar assembly magnetic fields. The choice of MCT position is justified, and parameters of its windings are determined; MCT construction and fastening are described, and a technique for reliable MCT output signal transmission under strong magnetic fields and with a specified protection threshold is suggested. These protections are currently the simplest and cheapest tool for preventing the complete destruction of an expensive busbar assembly in events of AFs during it.

26 June 2024 in Applied Sciences
Verified
Journal Article
Open access
PDF file
AMAnatoliy Manukovsky
Anatoliy Manukovsky
ASAigerim Bekenkyzy Sagyndyk
Aigerim Bekenkyzy Sagyndyk
AKAleksandr Kislov
Aleksandr Kislov
OTOlzhas Manarbekovich Talipov
Olzhas Manarbekovich Talipov
AMAlexey Manukovsky
Alexey Manukovsky
When operating solar–wind power plants (SWPPs) located in populated areas, cases of premature failure of expensive batteries and other power equipment often occur. The purpose of this study is to develop a wireless data acquisition system (DAS) for the operation of an SWPP with a feedback function to prevent material damage from the failure of power equipment and to increase the efficiency of natural energy use. The principles of constructing a DAS, free from some of the disadvantages of analogues, are described in this paper. Intelligent wireless current and voltage sensors and a device for receiving and recording data with an additional feedback function have been developed, providing real-time feedback when the measured parameters go outside the norm. Measurement data are displayed on the laptop screen and alphanumeric display and stored on the hard drive along with timestamps and current event messages. An example of using a reverse communication channel to implement the functions of backup battery protection and to switch SWPP loads is described. The principles and methods proposed in this article are suitable for constructing systems for remote measurements of any physical quantities; therefore, the scope of application of the described system can be significantly expanded.