This study examines the behavior and control of zero-sequence parameters in IT-type electrical networks under conditions of capacitive insulation asymmetry and complex asymmetric faults on the power receiver side. Existing methods of zero-sequence analysis typically address either symmetrical network conditions or single-phase earth faults in isolation, and they often neglect the combined effects of conductor breakage, transient fault resistance, and capacitive unbalance. To overcome these limitations, this work develops an analytical model based on the general theory of electrical engineering and symmetrical components, enabling a unified description of zero-sequence voltages and currents that incorporates both insulation asymmetry and compound fault scenarios. The model establishes closed-form relationships linking zero-sequence quantities to network parameters, power receiver characteristics, and transient resistances at the fault point. The results demonstrate several previously unreported effects, including a 180° vector shift and nearly 50% reduction in zero-sequence voltage and current magnitudes during simultaneous conductor breakage and earth faults compared with conventional single-phase faults—phenomena that critically influence the correct setting of protection devices. The study further shows that capacitive insulation asymmetry alone may generate zero-sequence voltages sufficient to trigger earth-fault protection regardless of the neutral grounding mode. These findings reveal increased risks of fault escalation, misoperation of existing protection systems, and prolonged unsafe touch voltages. Overall, the derived dependencies provide a new analytical basis for improving the design and coordination of protection systems in IT-type networks.
27 June 2024 in Electrical Engineering and Power Engineering
Purpose. Determination of the influence of network parameters with different neutral modes on the zero-sequence voltage Methodology. The research methodology is based on the general theory of electrical engineering and, in particular, on the method of symmetrical components. Findings. A mathematical model has been developed to establish the nature of the zero-sequence voltage change for different modes of the network neutral. The value of the zero-sequence voltages and the angles between the phase voltage vector with asymmetry and the zero-sequence voltage vector depending on the capacitive asymmetry, capacitance and active resistance of the network insulation for different neutral modes are established. Originality. Conducted studies have shown that the largest increase in the zero-sequence voltage is observed at the asymmetry capacity, which is 10...30% of the network insulation capacity. Moreover, the relative capacitive asymmetry of the insulation when changing the values of the capacitance of the network relative to the ground has the most significant effect on the value of the zero-sequence voltage in networks with a compensated neutral and is practically excluded when the neutral of the network is completely isolated relative to the ground. Practical value. For real parameters of the network, based on the results of theoretical and experimental studies, it is possible to judge the efficiency of existing protection devices and use them in the development of new principles and protection devices.