Optimal Network Reconfiguration (NR) is a well-accepted approach to minimize power loss and enhance voltage profile in the Electrical Distribution Networks (EDN). Since the NR problem contains huge combinational search space, most researchers consider the meta-heuristic techniques to attain NR solution. However, these meta-heuristic techniques do not guarantee to obtain the optimal solution besides they require large processing time to converge. This is mainly due to (1) random initialization and updating of population and (2) the continuous verification of population during the search process. With the aim of reducing the computational time and improving the consistency in obtaining the optimal solution as well as minimizing power loss and enhancing the voltage profile of the EDN, this work proposes a new method based on two-stage optimizations. The proposed method introduces an approach to simplify the network into simplified network graph. Then, this approach is utilized for guided initializations and generations of the population and for the proper population’s codification. The proposed method is implemented using the firefly algorithm and verified on 33-bus and 118-bus test systems. The results show the ability of the proposed method to obtain the optimal solution within fast computational time and with superior consistency compared to the conventional methods.
18 March 2025 in International Journal of Renewable Energy Development
Elevated winding insulation temperature, driven by harmonic distortions, is a key factor in transformer lifespan reduction. Conventional models often oversimplify the effect of combined current and voltage harmonics. This paper proposes an electro-thermal modeling approach, incorporating dual heat sources from core and winding domains, to enhance HST estimation in distribution transformers affected by photovoltaic-induced (PV)-induced harmonic losses. A sophisticated numerical approach, Finite Element Analysis (FEA), is employed using COMSOL Multiphysics software, with a 250-minute time-dependent study assessing thermal effects. The results, verified against a mathematical model approach based on IEEE C57.110-2018 guidance, demonstrate that higher levels of harmonics lead to a rapid increase in HST, accelerating the time to reach the aging factor temperature and consequently diminishing the transformer’s operational lifespan. Specifically, the per-unit life of the transformer decreases from 0.219 in Case 1 to 0.154 in Case 2 and 0.027 in Case 3, while the aging acceleration factor increases from 4.310 to 5.683 and 21.7, respectively. The methods showed over 95% alignment with the mathematical modeling approach, confirming the model’s precision in its predictive capability. The novelty of this study lies in its enhanced electro-thermal framework, which overcomes the limitations of conventional methods by integrating dual heat sources and providing a refined assessment of transformer aging under harmonic distortions. This advancement offers a more precise and computationally efficient approach for assessing transformer thermal stress under harmonic distortions.