Ahsanullah Memon

Mr. Ahsanullah Memon

orcid

Research Focus & Metrics

Academic Career Length

6Years (2021-Present)

(Calculated once Scilit publication data is synced: current year − year of first publication + 1)

Representative Publications

View All Publications
21 October 2021 in International Transactions on Electrical Energy Systems
Verified
Journal Article
Closed access
PDF file
AMAhsanullah Memon
Ahsanullah Memon
MMMohd Wazir Bin Mustafa
Mohd Wazir Bin Mustafa
TJTouqeer Ahmed Jumani
Touqeer Ahmed Jumani
MOMohammed Olatunji Obalowu
Mohammed Olatunji Obalowu
NMNajeeb‐Ur‐Rehman Malik
Najeeb‐Ur‐Rehman Malik

11 June 2021 in Electronics
Verified
Journal Article
Open access
PDF file
AMAhsanullah Memon
Ahsanullah Memon
MMMohd Wazir Mustafa
Mohd Wazir Mustafa
MAMuhammad Naveed Aman
Muhammad Naveed Aman
AHAbdul Hafeez
Abdul Hafeez
MUMukhtar Ullah
Mukhtar Ullah
Brushless doubly-fed induction generators have higher reliability, making them an attractive choice for not only offshore applications but also for remote locations. These generators are composed of two back-to-back voltage source converters, a grid side converter and a rotor side converter. Existing techniques use the rotor side converter for reactive current control; however, it is more suitable for stabilizing steady state behavior. In order to stabilize the voltage fluctuations at the point of common coupling (PCC) due to sudden inductive load introduction, the grid side converter may be a better choice due to faster response and higher control bandwidth. Therefore, this paper proposes a control scheme for the grid side converter to suppress the PCC voltage fluctuations when a large inductive load is suddenly connected. The proposed technique is based on an analytical model of the transient behavior of the voltage drop at the PCC. The analysis shows that reactive current control using the grid side converter introduces a double fundamental frequency component to the PCC voltage. To block this harmonic, we designed a notch filter. The simulation results in Matlab/Simulink show that the proposed technique can not only significantly reduce the voltage drop but also results in an 82% reduction in voltage distortion at the PCC.

24 September 2022 in International Transactions on Electrical Energy Systems
Verified
Journal Article
Open access
PDF file
ZLZohaib Hussain Leghari
Zohaib Hussain Leghari
SHSaddam Hussain
Saddam Hussain
AMAhsanullah Memon
Ahsanullah Memon
AMAbdul Hakeem Memon
Abdul Hakeem Memon
ABAshfaque Ahmed Baloch
Ashfaque Ahmed Baloch
This paper proposes parameter-free two best-worst optimizers (BWOs) that combine the searching capabilities of Jaya and Rao-1 algorithms to intensify their exploration and exploitation capabilities. For the proposed first optimizer, BWO-1, parallel taxonomy has been adopted for the Jaya and Rao-1 combination to obtain dual sets of updated solutions for a given current solution set. For the proposed second optimizer, BWO-2, along with the parallel taxonomy, a subloop of random scaling factors has been introduced in the solution updating mechanism of both standard Jaya and Rao-1 algorithms to generate multiple sets of updated solutions in a single iteration. The best solutions from obtained multiple solution-sets will survive only and lead to the next iteration. Hence, the proposed solution updating mechanisms for BWO-1 and BWO-2 increase the probability of getting a quality solution under set conditions. The ability and scalability of BWO-1 and BWO-2 were assessed, solving the optimization problem of power loss reduction and voltage deviation minimization in the IEEE 33-bus and 69-bus test systems. The results show that the BWO-2 exhibited a lead of 2.97%, 1.83%, and 0.72% over the Rao-1, Jaya, and BWO-1 techniques, respectively. Besides, the BWO-2 achieves up to 38.76% more reduction in power losses against the existing standard, improved, and hybrid optimization techniques.

23 July 2021 in Energies
Verified
Journal Article
Open access
PDF file
AMAhsanullah Memon
Ahsanullah Memon
MMMohd Wazir Mustafa
Mohd Wazir Mustafa
MAMuhammad Naveed Aman
Muhammad Naveed Aman
MUMukhtar Ullah
Mukhtar Ullah
TKTariq Kamal
Tariq Kamal
AHAbdul Hafeez
Abdul Hafeez
Brushless doubly-fed induction generators have higher reliability, making them an attractive choice for not only offshore applications but also for remote locations. These machines are composed of two back-to-back voltage source converters: the grid side converter and the rotor side converter. The rotor side converter is typically used for reactive current control of the power winding using the control winding current. A low voltage ride through (LVRT) fault is detected using a hysterisis comparison of the power winding voltage. This approach leads to two problems, firstly, the use of only voltage to detect faults results in erroneous or slow response, and secondly, sub-optimal control of voltage drop because of static reference values for reactive current compensation. This paper solves these problems by using an analytical model of the voltage drop caused by a short circuit. Moreover, using a fuzzy logic controller, the proposed technique employs the voltage frequency in addition to the power winding voltage magnitude to detect LVRT conditions. The analytical model helps in reducing the power winding voltage drop while the fuzzy logic controller leads to better and faster detection of faults, leading to an overall faster response of the system. Simulations in Matlab/Simulink show that the proposed technique can reduce the voltage drop by up to 0.12 p.u. and result in significantly lower transients in the power winding voltage as compared to existing techniques.

1 June 2022 in International Journal of Applied Power Engineering (IJAPE)
Verified
Journal Article
Open access
PDF file
OMOlatunji Obalowu Mohammed
Olatunji Obalowu Mohammed
MMMohd Wazir Mustafa
Mohd Wazir Mustafa
SSSani Salisu
Sani Salisu
AMAhsanullah Memon
Ahsanullah Memon
SHSaddam Hussain
Saddam Hussain
OIOladimeji Ibrahim
Oladimeji Ibrahim
Available transfer capability (ATC) is an important metric used to measure the techno-economic viability of the transmission networks. Several methods have been presented in literature for ATC assessment, however, only some few articles incorporate CBM in ATC calculation and those few papers only considered conventional power generation sources in CBM evaluation. CBM is a function of the reliability of generating units. This paper presents the inter-area CBM calculation in the presence of wind energy source using graph theory technique and the results are incorporated in ATC computation using repeated power flow. CBM is incorporated in ATC computation as non-recallable and recallable power transfers. The results with and without CBM incorporation, in the presence of wind power system, are compared. The contribution of the paper is to study the influence of wind power (WP) integrated CBM on ATC evaluation. The results showed that the incorporation of CBM, in the presence of renewable energy, has a significant influence on ATC, without which ATC would be inaccurately estimated. Simulations using IEEE 24-Bus RTS is used to implement the proposed approach. This approach can be employed by transmission operators to assess the technoeconomic viability of the power network for possible power transactions.

1 March 2024 in International Journal of Power Electronics and Drive Systems (IJPEDS)
Verified
Journal Article
Open access
PDF file
AKAttaullah Khidrani
Attaullah Khidrani
Raja Masood LarikRaja Masood Larik
Raja Masood Larik
AMAhsanullah Memon
Ahsanullah Memon
IBIrfan Ahmed Bajkani
Irfan Ahmed Bajkani
Sajid Hussain QaziSajid Hussain Qazi
Sajid Hussain Qazi
With the rapidly depleting natural energy resources and increasing population worldwide, the calls for more energy demand have risen globally. In this vein, the world is transitioning from traditional to renewable energy sources (RES) to meet the required demands. However, the (RES), due to its variable nature, has voltage stability and power quality issues that need to get minimized to enhance the reliability of the (RES) system. This paper reviews the voltage stability and quality issues in the AC distribution system based on renewable energy sources (RES). Initially the renewable energy sources and problems associated with renewable energy sources are discussed. This article gives an overview of voltage control strategies based on local as well as communication-based phenomenon for distribution networks. In this review a hybrid solar photovoltaic and wind system is used to generate the power of 3-5 kW. A voltage controller topology is suggested using MATLAB/Simulink for enhancing voltage stability of the system. It is suggested that a voltage stability controller can be designed using recommended topology by using Arduino with pulse width modulation technique. Thus, by measuring and correcting real-time voltage instability values of the system, the system can be made more reliably secure, efficient, and stable than the previously proposed renewable AC distribution systems.