Kongming Sun

Mr. Kongming Sun


Research Focus & Metrics

Academic Career Length

10Years (2017-Present)

(Calculated once Scilit publication data is synced: current year − year of first publication + 1)

Representative Publications

View All Publications
18 October 2018 in IEEE Transactions on Energy Conversion
Verified
Journal Article
Closed access
ZZZhiming Zhang
Zhiming Zhang
QCQing Chen
Qing Chen
RXRanran Xie
Ranran Xie
KSKongming Sun
Kongming Sun
Compared with the AC microgrids, the advantages of DC microgrids are notable. However, the development of DC microgrids is being constrained by the lack of mature protection schemes. As the foundation of designing protection schemes, the existing fault analysis almost all focused on the fault characteristics of voltage source converters (VSCs) and ignored other generators. While, in DC microgrids with high permeability of photovoltaic (PV) powers, the impacts from PV powers should be paid enough attention. In this paper, the cable fault characteristics of the PV powers are analyzed in detail and both the pole-to-ground fault and the pole-to-pole fault are involved. The fault processes are divided into several stages and the fault circuits and main equations are given for each stage. All the analysis are verified by the simulation model based on the PSCAD/EMTDC and with the help of simulation results, the two main challenges the protection system confronted with are emphasized and impacts of fault distance are analyzed. Finally, the paper proposes to employ a more reasonable converter structure and a transverse differential protection to overcome the main challenges, and the methods effectiveness is verified by the simulation.

25 July 2017 in Energies
Verified
Journal Article
Open access
PDF file
KSKongming Sun
Kongming Sun
QCQing Chen
Qing Chen
PZPu Zhao
Pu Zhao
The increasing use of modern measuring devices, such as Feeder Terminal Units (FTUs), on power networks can provide multiple types of information for fault location on distribution systems. Using these devices, in this paper, a novel automatic matrix-based algorithm for the identification and isolation of faulted feeder sections on distribution systems is proposed. The algorithm works in two stages: the first stage automatically identifies the radial feeders that make up the whole system and represents the feeders’ topology in matrix form; and the second stage automatically identifies the faulted section of the identified feeder and opens the relevant switches to isolate it. The algorithm can be applied to single and multiple faults, as it operates using measuring device information and detecting the status of switch devices. It does not require any electrical parameters and it is not affected by the fault type or fault resistance. The algorithm was thoroughly tested using a large distribution system and was found to efficiently identify and isolate the faulted feeder section in each case.

31 July 2017 in Energies
Verified
Journal Article
Open access
PDF file
PZPu Zhao
Pu Zhao
QCQing Chen
Qing Chen
KSKongming Sun
Kongming Sun
CXChuanxin Xi
Chuanxin Xi
This paper proposes a fault-location method for voltage-source converter (VSC)-based high-voltage direct current (VSC-HVDC) systems. This method relies on the current frequency components generated by faults in the cable, and requires the arrival time of the frequency components at two terminals. The S transform is a time–frequency analysis tool that is superior to the wavelet transform in some respects. Therefore, the S transform was employed to determine the arrival time in this paper. To obtain a reliable criterion, a novel phase-mode transform method for bipolar cables was developed, and the propagation characteristics of the current frequency components through out the cable were analyzed. A two-terminal VSC-HVDC system was modeled in power system computer aided design/electromagnetic transients including DC (PSCAD/EMTDC). Various faults under different conditions were simulated on the basis of this model, and the simulation results verified a high accuracy, robustness against fault-resistance, and noise immunity of the proposed method.

17 June 2022
Verified
Conference Paper
Closed access
ZLZhengtang Liang
Zhengtang Liang
SLSujie Liang
Sujie Liang
QZQiang Zhang
Qiang Zhang
KSKongming Sun
Kongming Sun
NLNa Li
Na Li
YLYundun Li
Yundun Li
In order to adapt to the mode of no-operator substation and meet the requirements of monitoring and operation and maintenance of substation monitoring system remotely, a method of accessing telecontrol configuration description file (RCD, Remote Configuration Description) based on DL/T476 protocol is proposed in this paper. This method makes full use of the hardware facilities of the dispatching master station-substation, does not need additional hardware equipment, and only makes a minor upgrade to the program of dispatching master station and the substation data communication gateway server, which can realize remotely access RCD files of substations from the dispatching master station. The effectiveness of the method is verified by laboratory tests and pilot applications in Linyi Yuquan Station.

26 September 2026 in Energies
Verified
Journal Article
Open access
PDF file
YHYanqi Hou
Yanqi Hou
KLKuan Li
Kuan Li
YLYudun Li
Yudun Li
KSKongming Sun
Kongming Sun
With the increasing integration of distributed generation, energy storage, and flexible loads, active distribution networks have gained multiple fault-recovery options, including network reconfiguration, islanded operation, and coordinated source–load regulation. However, existing studies often lack an effective link between system-level restoration decisions and resource-level execution. To address this issue, this paper proposes a two-layer collaborative optimization method for multi-period fault recovery with fast decomposition. The upper layer develops a multi-period restoration model that jointly optimizes network reconfiguration, load restoration targets, and fault repair sequences, with the objectives of minimizing load loss and recovery cost while maximizing continuous power-supply duration. The model incorporates load priorities, switch operations, distributed generation, energy-storage states, flexible-load response, main-grid support, and inter-period coupling constraints. Based on the restoration targets generated by the upper layer, the lower layer applies a fast sort-and-fill decomposition strategy to allocate regulation demands among photovoltaic generation, wind power, energy storage systems, flexible loads, and main-grid support, thereby forming a closed-loop coordination mechanism between restoration planning and resource execution. The proposed method is validated on a modified IEEE 33-bus active distribution network under multi-period fault scenarios. Results show that the load restoration rate is 88.78% in Period 1 and reaches 100% from Period 2 onward. Compared with static restoration, unserved energy decreases from 4.6896 MWh to 0.3113 MWh, while restored energy increases from 8.2505 MWh to 12.6288 MWh. Over 1000 randomized feasible operating points, the maximum absolute objective gap between the proposed sort-and-fill procedure and direct LP re-optimization is 7.55×10−14%, and the maximum power-balance error is 2.73×10−12 kW. These results demonstrate that the proposed method improves restoration effectiveness while reproducing the exact lower-layer LP solution within numerical precision.