This paper proposes an analytic method for the amplitude estimation of the forced oscillation under stochastic continuous disturbances (SCDs). There is considerable interest in the integration of intermittent renewable energy resources into a power system, which leads to the power system in an environment with SCDs. Thus, the forced oscillation issues under SCDs are of concern. In this paper, the SCDs are described as continuous-time stochastic processes, and then the systems under SCDs are modeled by stochastic differential algebraic equations. Furthermore, by employing stochastic theory, an efficient analytic method for calculating the statistics of system states during the forced oscillation is proposed. Moreover, a novel forced oscillation phenomenon, which presents system states oscillate with stationary distributions under SCDs, is clearly characterized and theoretically explained. Based on the proposed analytic method, a scheme is put forward to estimate amplitudes of system states during forced oscillation under SCDs. Finally, compared to Monte Carlo simulation, the proposed scheme has two significant advantages. First, the proposed scheme offers a fast and effective solution for engineering applications. Second, the impact mechanism of SCDs on forced oscillation in power system is clearer, by the proposed scheme.
According to the monitoring of the wide area measurement system, inter-area oscillations happen more and more frequently in a real power grid of China, which are close to the forced oscillation. Applying the conventional forced oscillation theory, the mechanism of these oscillations cannot be explained well, because the oscillations vary with random amplitude and a narrow frequency band. To explain the mechanism of such oscillations, the general forced oscillation (GFO) mechanism is taken into consideration. The GFO is the power system oscillation excited by the random excitations, such as power fluctuations from renewable power generation. Firstly, properties of the oscillations observed in the real power grid are analyzed. Using the GFO mechanism, the observed oscillations seem to be the GFO caused by some random excitation. Then the variation of the wind power measured in this power gird is found to be the random excitation which may cause the GFO phenomenon. Finally, simulations are carried out and the power spectral density of the simulated oscillation is compared to that of the observed oscillation, and they are similar with each other. The observed oscillation is thus explained well using the GFO mechanism and the GFO phenomenon has now been observed for the first time in real power grids.
The increasing integration of renewable energy has led to power systems characterized by a high penetration of renewable energy sources (RES) and power electronic devices (PEDs). However, wide-band oscillation phenomena caused by RES grid integration have emerged and propagated through transmission networks. Notably, large-scale renewable energy bases located in remote areas are typically connected to the main grid via long-distance AC transmission lines. These lines exhibit an inter-harmonic amplification effect, which may exacerbate the propagation and amplification of wide-band oscillations, posing significant risks to bulk power-grid stability. This paper establishes impedance models of long-distance AC transmission lines and asynchronous motors under wide-band oscillation frequencies, and derives equivalent line parameters mathematically to reveal the oscillation amplification problem of long-distance renewable energy oscillation transmission through AC transmission lines. A transfer coefficient is defined to quantify inter-harmonic current amplification. A single-machine-load model is developed in MATLAB/Simulink to validate the proposed model. Furthermore, the influence of line parameters on oscillation amplification is analyzed, and a suppression strategy is proposed. This study provides valuable insights for the parameter design of long-distance transmission lines in renewable energy integration scenarios, as it helps mitigate potential inter-harmonic amplification risks by reducing the peak values of the transfer coefficient.
The increasing penetration of renewable energy exposes doubly fed induction generator (DFIG)-based wind power systems to weak-grid conditions, making them susceptible to low-frequency and subsynchronous oscillations. Although grid-forming (GFM) control enhances weak-grid adaptability, the resulting high-order small-signal model complicates stability analysis and controller design. This paper establishes a 15th-order state-space model for a GFM-DFIG system. Eigenvalue analysis is performed to identify the dominant oscillation modes and to reveal their sensitivity to controller parameters and grid strength. To reduce computational burden, a model order reduction method combining singular perturbation theory and participation factor analysis is proposed, yielding an eighth-order model that preserves dominant oscillatory characteristics. An additional damping control strategy is then designed using the reduced model. Simulations validate the reduced model’s accuracy and demonstrate the damping control’s effectiveness in mitigating oscillations. This paper provides an effective framework for stability analysis, reduced-order modeling, and damping control design for GFM-DFIG systems.
With the construction of the UHV (Ultra High Voltage) AC/DC hybrid power grid and the large-scale access to renewable energy such as wind power, frequency dynamic fluctuation has become a prominent problem affecting the safe and stable operation of large power grids. The expansion of the scale of the power system makes it impossible to use traditional fine modeling to analyze the power system. In order to reduce the calculation scale and storage capacity of power system frequency dynamic simulation, it is necessary to make appropriate equivalent simplification of the external system, so the appropriate dynamic equivalent method is of great significance. This paper mainly studies the equivalent model suitable for frequency dynamic analysis of large power grids. Firstly, the typical models of generator set and load are simplified, and the parameters that have a great influence on frequency in the simplified model are obtained through characteristic analysis. Then, a dynamic aggregation method of generator governor and prime mover parameters and load parameters based on regulation performance weighting (the parameters of the generator or load are weighted and summed according to its regulation ability on the system) is proposed. This method is applied to the simulation example of the East China Power Grid. The simulation proves that the frequency of the East China Power Grid before and after equivalence can be consistent under four different faults, which verifies the effectiveness of the equivalent method proposed in this paper in the frequency dynamic analysis of large power grids.
To enhance the adaptability of grid partitioning under transient scenarios, this paper proposes a two-stage dynamic partitioning strategy based on structure–function coupling. Electrical coupling strength is first characterized using short-circuit impedance and the sensitivity between reactive power and voltage, while transient voltage correlation is incorporated through cosine similarity as edge weights in a graph model. Grid partitioning is then conducted by maximizing modularity through a staged approach that ensures network connectivity and automatically determines partition numbers. Case studies on the modified IEEE 39-bus system demonstrate that compared with transient voltage-based partitioning and conventional complex network methods, the proposed approach improves modularity by 69%, reduces the maximum post-fault voltage deviation by 38.6%, and achieves the highest regional decoupling rate. The result shows strong intra-regional cohesion and weak inter-regional connectivity, verifying the strategy’s effectiveness in enhancing adaptability and decoupling under transient conditions.