Small-signal instability issues will occur in the DC microgrid when the high-frequency oscillation peaks of the voltage closed-loop transfer function are not effectively suppressed. To ensure the small-signal stability of DC microgrids, the concept of a small-signal stability domain for voltage control parameters is proposed. Based on the voltage closed-loop transfer function, a small-signal-stability-domain-solving algorithm is proposed. With this stability domain, the impact of voltage-proportional coefficient and voltage-integral coefficient on oscillation frequency (or damping factor) is quantitatively analyzed. In addition, the influence of current control parameters on the small-signal stability boundary is also analyzed. With the introduction of this stability domain, a design method for voltage control parameters has been proposed. The voltage control parameters, which are quantitatively designed by this method, are able to maintain the small-signal stability of the system. Finally, based on the RT-BOX hardware-in-the-loop experimental platform, a switching model for a typical DC microgrid is established. Additionally, the effectiveness of the proposed algorithm and designed control parameters is verified by multiple sets of experimental results.
High penetration of distributed photovoltaic (PV) generation has transformed active distribution networks into inverter-dominated systems, where maintaining voltage stability, minimizing power losses, and maximizing renewable utilization under uncertainty remain significant challenges. Conventional centralized optimal power flow (OPF) and ADMM-based distributed optimization methods suffer from scalability limitations, high computational latency, and reliance on accurate system models, while single-agent reinforcement learning approaches such as PPO struggle with non-stationarity and lack of coordination in multi-inverter settings. To address these limitations, this paper proposes a coordinated control framework based on Multi-Agent Proximal Policy Optimization (MAPPO) for photovoltaic inverter clusters. By adopting centralized training with decentralized execution, the proposed approach enables effective coordination among heterogeneous inverter agents while preserving real-time autonomy. The framework explicitly incorporates network-level objectives, inverter operational constraints, and stochastic irradiance and load uncertainties, allowing agents to learn adaptive and robust control strategies. Simulation studies on a modified IEEE 33-bus active distribution network demonstrate that the proposed MAPPO-based method reduces voltage deviations by more than 40%, decreases network losses by approximately 25%, and lowers photovoltaic curtailment ratios by nearly 50% compared with centralized optimization approaches. In addition, MAPPO achieves significantly faster and more stable convergence than independent PPO under highly variable operating conditions.b These results indicate that MAPPO provides a scalable and resilient alternative to conventional optimization and single-agent learning methods, offering a practical pathway to enhance hosting capacity, operational robustness, and renewable integration in future active distribution networks.
The low-voltage distribution system (LVDS) is confronted with high-frequency oscillation instability issues due to the negative impedance of constant power loads. To address this, a virtual inertia equivalent modeling method is proposed in this paper, and a reduced-order model along with its transfer function for the LVDS is established. On this basis, a method for solving the feasible region of virtual inertia parameters is proposed. Through this feasible region, reasonable droop coefficients and corner frequencies can be designed from the perspective of small-signal stability. Finally, the switching model of LVDS and its equivalent model are built using the RT-box HITL platform. Multiple sets of experimental results have verified the effectiveness of this feasible region.
The mismatch between the DC voltage control bandwidth and the low-pass filter control bandwidth results in a non-virtual inertia phenomenon in the DC voltage of the DC microgrid. For this purpose, a transfer function model of the DC microgrid is established in this paper, and the causes of the non-virtual inertia phenomenon are explained from the perspective of control bandwidth. Secondly, a virtual inertia response criterion based on control bandwidth matching is presented in this paper. Then, the concept and solution method of the control bandwidth matching domain are also provided in this paper. This control bandwidth matching domain can not only effectively ensure the virtual inertia characteristics of the DC microgrid but also be used to evaluate the system’s virtual inertia strength under different low-pass filter control bandwidths. Experimental results show that when the ratio of the voltage control bandwidth to the low-pass filter control bandwidth is greater than 10, the DC microgrid presents virtual inertia characteristics; otherwise, it exhibits non-virtual inertia (damped oscillation) characteristics.
Extreme weather couples spatially correlated component damage with photovoltaic (PV) derating, changing electric-vehicle (EV) demand, repair delay, and time-varying network topology. This paper develops a coordinated restoration architecture for multi-area feeders containing PV, battery energy storage, and charging stations. Its weather-facing layer constructs joint outage-risk, renewable-error, charging-demand, and voltage-vulnerability descriptors. Those descriptors parameterize a two-stage mixed-integer second-order-cone program with a finite-support optimal-transport ambiguity set that remains well defined for discontinuous mixed-integer recourse. Regional actor–critic agents propose five-minute corrections around the hourly robust schedule; constrained projection, non-linear AC power-flow screening, emergency fallback, and margin-tightened re-optimization retain the authority to accept or reject each proposal. The evaluation uses public 33-node and 123-node feeders together with synthetic 240-node and 850-node stress networks. A pre-fit manifest allocates 240 records to training, 80 to validation, and 320 to final testing, while aggregate operational outcomes cover 50 random streams. Within this controlled benchmark, accepted schedules restore 93.6% of critical-load energy (SD 2.1 percentage points), serve 96.7% of total demand (SD 1.8 percentage points), retain 82–86% of EV service across hazard classes, and reduce the modeled 24 h objective by 25.8% relative to deterministic dispatch. The full pipeline records two to four candidate-stage voltage-limit events by hazard, and 4.9% of candidates undergo tightened re-optimization before accepted schedules reach zero reported AC voltage-limit violations. Between-method comparisons are descriptive and unpaired; the larger synthetic cases are structural stress tests rather than feeder-transfer tests.
When droop control of virtual synchronous generators (VSGs) with rotational inertia is adopted in islanded alternating current (AC) microgrids, the coupling mechanism among reactive power loads, control parameters and system virtual inertia remains unclear, and there is a lack of quantitative evaluation schemes. To address this issue, this paper proposes a quantitative evaluation method for virtual inertia based on a reduced-order equivalent model. First, the control system of grid-forming converters is simplified to construct a reduced-order model for microgrid voltage support, and the analytical expression of voltage dynamics and the calculation formula of the system-level inertia time constant are derived. Subsequently, a three-dimensional response surface is utilized to multi-dimensionally analyze the influence laws of filter cutoff frequency, reactive power load, rotational inertia and damping coefficient on system inertia and steady-state voltage drop. Finally, a reduced-order model of the AC microgrid is established based on the RT-Lab hardware-in-the-loop (HIL) experimental platform, and multiple sets of results validate the correctness of the theoretical analysis.