The electrical distribution system, with its radial structure and passive nature, is prone to high power losses due to imbalanced load demand and inadequate reactive power, resulting in a poor voltage profile. This paper presents a novel metaphor-less RAO algorithm for the optimal sizing and location of Distributed Generation to achieve optimal penetration levels. This study introduces new location and size deviation indices to assess the impact of DG installation. The proposed methodology employs a multi-objective function that minimizes active and reactive power losses and maximizes the minimum voltage, using a weighted-sum approach. The method is applied to the IEEE-33 bus radial distribution system with various load models, including residential, commercial, industrial, and electric-vehicle battery-charging loads, as well as combinations of these models. The simulation results across various scenarios demonstrate the efficiency of the proposed algorithm at different DG penetration levels and for different load types and demand profiles. On the IEEE-33 bus, power losses were reduced to 48.70%, 64.56%, and 69.07% after DG allocation with unity, fixed, and optimal power factors, respectively, under the constant-load model. Additionally, the presented work determines the optimal range of power factor-based DG penetration for distinct load models and the role of DG allocation in the electrical distribution system during the critical emergency conditions of the COVID-19 pandemic.
1 January 2026 in IEEE Transactions on Power Delivery