Quality of power supply in power distribution systems requires continuous measurement using power quality analyzers installed in the grid. The paper reviews the published methods for optimal location of metering points in distribution systems in the context of power quality metering and assessment. Three methods have been selected for detailed analysis and comparative tests. It has been found that utilization of the methods is possible, but their performance varies highly depending on the test grid’s topology. Since the methods rely on the state estimation approach, their performance is strictly related to observability analysis. It has been found that standard observability analysis used for typical state estimation problem yields ambiguous results when applied to power quality assessment. Inherited properties of the selected methods are also analyzed, which allows for the formulation of general recommendations about optimal selection of metering points in a distribution system.
The presently observed rapid increase in photovoltaic (PV) micro-installation connections to low-voltage networks, resulting from numerous financial support programmes, European Union (EU) energy policy and growing social awareness of environmental and economic issues, raise the question if PV inverters widely available in EU market fulfil the numerous technical requirements specified in European and Polish regulations. The paper presents the results of an experimental study carried out on three PV Inverters widely available in the EU in accordance with the EU network code NC RfG, standard EN 50549-1:2019 and internal Polish distribution system operators’ (DSOs’) regulations, governing PV inverter cooperation with the low-voltage distribution network. The laboratory test stand scheme and its description are presented. In each test, at least one of the inverters encountered issues, either with the operation in required frequency ranges (one PV inverter), activating reactive power control modes (all three PV inverters), maintaining required power generation gradient after tripping (one PV inverter) or under-voltage ride through immunity (one PV inverter). The obtained results have shown that all tested PV inverters did not meet requirements that are the key to maintaining reliable and safe operation of transmission and distribution electrical networks.
The paper presents the results of an experimental study of 26 brand new photovoltaic (PV) inverters widely available for sale on the EU market; the study was conducted in 2021 by researchers at the AGH University of Science and Technology and Tauron Dystrybucja (Polish DSO). The purpose of the study was to compare and assess PV inverter performances in terms of their DC/AC conversion efficiencies, MPPT efficiencies, and harmonic current emissions. To examine the PV inverters, a laboratory test stand was prepared according to the standard EN 50530 and the technical report IEC/TR 61000-3-15. It was composed of a photovoltaic array simulator, a programmable regenerative AC voltage source, and a power analyzer. Each PV inverter was tested in various operating states determined by the DC voltage levels and the volume of active power generation. The results allowed for a benchmark assessment of PV inverters available on the market. The results showed how various energy efficiency indicators of individual PV inverters changed depending on their operating points. The results also revealed that, based on the performed harmonic emission tests, individual harmonics were within the normative requirements; however, in the case of several PV inverters, attention was drawn to the presence of relatively high switching frequency-related components exceeding permissible levels.
This paper describes a laboratory-based comparison of power quality class A analyzers, with respect to voltage harmonic distortion measurements. The tested measuring instruments were designed in accordance to the requirements of the IEC 61000-4-30 standard. The purpose of these tests was to assess the dispersion of results of analyzers connected to a common measuring point. The expectation is that simultaneous measurements of the same voltage signal should result in a readings dispersion not greater than ±5% of the measured value. The described tests are part of a complex evaluation of metrological properties of power quality analyzers carried out at the AGH University of Science and Technology, Krakow. Detailed results of harmonic tests, comparisons, and conclusions are presented.
Monitoring power quality (PQ) indicators is an important part of modern power grids’ maintenance. Among different PQ indicators, flicker severity coefficients Pst and Plt are measures of voltage fluctuations. In state-of-the-art PQ measuring devices, the flicker measurement channel is usually implemented as a dedicated processor subsystem. Implementation of the IEC 61000-4-15 compliant flicker measurement algorithm requires a significant amount of computational power. In typical PQ analysers, the flicker measurement is usually implemented as a part of the meter’s algorithm performed by the main processor. This paper considers the implementation of the flicker measurement as an FPGA module to offload the processor subsystem or operate as an IP core in FPGA-based system-on-chip units. The measurement algorithm is developed and validated as a Simulink diagram, which is then converted to a fixed-point representation. Parts of the diagram are applied for automatic VHDL code generation, and the classifier block is implemented as a local soft-processor system. A simple eight-bit processor operates within the flicker measurement coprocessor and performs statistical operations. Finally, an IP module is created that can be considered as a flicker coprocessor module. When using the coprocessor, the main processor’s only role is to trigger the coprocessor and read the results, while the coprocessor independently calculates the flicker coefficients.
The paper presents the results of an experimental study, which was conducted in 2021 and briefly presented at the conference CIGRE Paris Session 2022, as a part of a joint initiative for comparative studies of PV inverters, of AGH University of Science and Technology and Tauron Dystrybucja (Polish DSO). The study was performed on a representative sample of 29 brand new PV inverters, widely available for sale in the EU, from over 20 various manufacturers from and outside the EU. For the purposes of this research, all tested PV have been made available by their manufacturers or regional distributors, which confirms the origin of the devices from official distribution channels and their designation for the EU market. The conducted research covers the technical aspects of PV inverters’ operation and performance included in the NC RfG network code, technical standard EN-505049-1:2019, and internal regulations of distribution system operators governing PV inverter technical quality and its cooperation with the low-voltage distribution network. The national regulations may differ between individual EU member states. The paper describes the testing procedure, obtained results, conclusions, and recommendations for regulatory bodies and DSOs.