This paper presents a new investigation to detect various faults within the three-phase star and delta induction motors (IMs) using a frequency response analysis (FRA). In this regard, experimental measurements using FRA are performed on three IMs of ratings 1 HP, 3 HP and 5.5 HP in normal conditions, short-circuit fault (SC) and open-circuit fault (OC) conditions. The SC and OC faults are applied artificially between the turns (Turn-to-Turn), between the coils (Coil-to-Coil) and between the phases (Phase-to-Phase). The obtained measurements show that the star and delta IMs result in dissimilar FRA signatures for the normal and faulty windings. Various statistical indicators are used to quantify the deviations between the normal and faulty FRA signatures. The calculation is performed in three frequency ranges: low, middle and high ones, as the winding parameters including resistive, inductive and capacitive components dominate the frequency characteristics at different frequency ranges. Consequently, it is proposed that the boundaries for the used indicators facilitate fault identification and quantification.
The industry has widely accepted Frequency Response Analysis (FRA) as a reliable method to detect power transformers mechanical deformations. While the FRA technique has been recommended in recent literature as a potential diagnostic method to detect internal faults within rotating machines, detailed feasibility studies have not been fully addressed yet. This paper investigates the feasibility of using the FRA technique to detect several short circuit faults in the stator winding of three-phase induction motors (TPIMs). In this regard, FRA testing is conducted on two sets of induction motors with various short circuit faults. Investigated faults include short circuits between two phases, short circuit turns within the same phase, phase-to-ground, and phase-to-neutral short circuit. The measured FRA signatures are divided into three frequency ranges: low, medium, and high. Several statistical indicators are employed to quantify the variation between faulty and healthy signatures in each frequency range. Experimental results attest the feasibility of the FRA technique as a diagnostic tool to detect internal faults in rotating machines, such as induction motors.
Frequency Response Analysis (FRA) technique has been recognized by worldwide utilities as a matured technology to assess the mechanical integrity of power transformers. While some industrial critical assets such as induction motors have the same construction principle as power transformers, the application of FRA technique to induction motors has not yet been fully explored. This paper presents analogical experimental studies for the application of FRA on power transformers and induction motors. For a consistent analogy, the FRA technique has been employed to detect short and open circuit turns in both appliances, which helps explore a wider scope of the FRA applications on rotating machines. In this regard, experimental FRA measurements are performed on an 11/0.415 kV, 500 kVA, three-phase distribution transformer and a 5.5 HP three-phase induction motor. Several short and open circuit faults are staged on the windings of both tested equipment and the FRA signature is recorded and compared with the reference signature at no fault. To quantify the impact of faults on the FRA signature, several statistical indicators are used and threshold limits for these indicators are proposed to automate the interpretation process. Results reveal a good correlation between the FRA signatures of induction motors and power transformers that attests to the feasibility of using FRA technique to detect various faults within large rotating machines.
Constructions expose the risk of fault current and lightning since it does not have an appropriate grounding system. In the grounding systems, the electrode affects the system reduction so that additive materials play an essential role in improving electrode resistivity. This paper conducted an experimental study on the Bio-degradable recycled waste materials to improve ground grid resistance reduction. This study contributes to the value of waste materials to improve ground grid resistance reduction. The objective is to investigate the three types of palm oil waste that behave as additive materials to enhance the performance of the grounding system by lowering the soil resistance value. This grounding system is designed from meshes of aluminum electrode material with 1m2 and 0.5m depth. The measurement is performed using the fall of potential FOP technique and recorded within 15 days. The investigated lowest resistive materials results are then compared with the results from ground enhancement material (GEM). The results are compared to give a comprehensive view of each different material advantage in improving grounding grid reduction. The results obtained show that the palm oil ashes waste has better performance in reducing grounding resistance. This study also indicates that the configuration of the aluminum meshes able to reduce grounding resistance.